In-Wall and Ceiling Mount Sensors in both PIR (infrared) and Dual (PIR/Ultrasonic) Technologies can monitor virtually any area within a building, making Intermatic your best source when integrating lighting strategies in any retrofit or new construction project. Intermatic sensors are Title 20 compliant and can be used to achieve LEED certification.

Engineered and tested for long-lasting performance.

Our occupancy sensors have been designed and strenuously tested to ensure their dependability and compatibility with any lighting type including LED. In fact, they have achieved some of the highest ratings in the industry, including a 5 A Electronic Ballast Rating and meeting the NEMA 410 Standard.

They utilize zero-crossing technology to suppress inrush current impact. This provides reliable ON/OFF sensing no matter the lighting technology, whether older magnetic models or new electronic drivers and ballasts.



Commercial-Grade Sensors

Ceiling Mount and In-Wall Switch Sensors

Intermatic’s line-up of ceiling mount sensors and in-wall switches are simple to install, so they can get to work quickly, helping to save energy, enhance security, and add convenience in all types of facilities: offices, industrial/warehouses, schools, hospitals, nursing homes, and rehabilitation centers.

Click here to view the full product line.

Features

Features:

    • Variety of coverage options to best meet the environment
    • Zero-crossing technology for long life and performance
    • Adjustable ambient light sensor override
    • “No neutral wire required” models for retrofit applications
    • User-selectable Vacancy or Occupancy switch mode available on IOS-DSR/DOV/DDR models
    • High-Bay Fixture Mount Sensor detects from 15 to 50 ft.
    • In-Wall Switches come with standard decorator wall plate
    • Incandescent/Fluorescent/CFL/LED compatible

Commercial-Grade Sensor Applications

 
In-Wall Mount Ceiling Mount
IOS-DOV-DT IOS-DOV / IOS-DSR
/ IOS-DDR
IOS-CMP-DT-U IOS-CMP-DT-LV IOS-CMP-U /
IOS-CMP-LV
IOS-HB-U
Dual PIR Dual PIR
Partitioned Restroom
Office Space w/ Cubicles
Storage Room
Library
Waiting Room
Laundry Room
Private Office
Copy Room 
Partitioned Restroom
Office Space w/ Cubicles
Storage Room
Library
Waiting Room
Partitioned Restroom
Storage Room
Waiting Room
Conference Room
Classroom
Large Open Areas
Breakroom
Warehouse
Manufacturing

back to top

Residential-Grade Sensors

In-Wall Occupancy and Vacancy Sensor Switches

Intermatic’s Occupancy Sensors are designed to save energy, add security, and compliment the aesthetics of single or multifamily homes. They are simple to install, as many do not require a neutral wire. There are models to control both electronic and magnetic ballasts and all meet California Title 20 requirements. All models incorporate passive infrared (PIR) technology to detect the heat that is naturally generated by people for ON and OFF activation.

Click here to view the full product line.

Features

Features:

    • Adjustable PIR sensitivity
    • Adjustable time delay 15 sec to 30 min
    • Adjustable ambient light sensor override
    • Incandescent/ Fluorescent/CFL/LED compatible models
    • “No neutral wire required” models available for retrofit
    • Come with standard decorator wall plate

back to top
Learn More

The right technology for the space.

Any object or person naturally emits radiation in the infrared range, known as the ordinary heat radiated by each element. Our range of sensors detects the presence and movement of people in a room, space, or immediate vicinity. Smart technology discerns even fine motor movements, so lights stay on when needed and turn off when vacated to conserve energy.


The differences between Passive Infrared (PIR) and Dual (PIR/Ultrasonic) technology.

PIR Technology
Dual Technology

Passive infrared (PIR) technology detects the difference in heat energy a person in motion generates in contrast to the elements surrounding them in a confined space. To detect presence PIR needs line of sight to a person.

Dual (PIR/Ultrasonic) technology combines PIR with Ultrasonic technology. Ultrasonic utilizes wave analysis and Doppler sound waves to detect differences in energy from different phenomenon. The combination of the two technologies enhances responsiveness for
maximum system reliability. 


Using PIR or Dual Technology Based on Room Layout*

Non-partitioned Restroom
In-Wall Sensor with PIR Technology

Non-partitioned Restroom with PIR Technology
IOS-DSIF-WH

Partitioned Restroom
In-Wall Sensor with Dual Technology

Partitioned Restroom with Dual Technology
IOS-DOV-DT-WH

Office Space with Cubicles
Ceiling Mount Sensor with Dual Technology

Office Space with Dual Technology
 IOS-CMP-DT-U

Conference Room
Ceiling Mount Sensor with PIR Technology

Conference Room with PIR Technology
 IOS-CMP-U

   


Installation Tips:
  • Do not install near vents; refer to instruction sheets
  • Make sure sensor is not blocked by objects or doors
  • When installing multiple sensors, overlap walkway coverage, to avoid non-triggers
back to top



Commercial-Grade In-Wall Sensor Comparison Guide


LED
IOS-DOV-DT-WH
IOS-DOV-NL
IOS-DOV
 IOS-DSR IOS-DDR
Model # IOS-DOV-DT IOS-DOV-NL IOS-DOV IOS-DSR IOS-DDR
Switch Type

Occupancy 
or Vacancy

User-selectable Vacancy or Occupancy with Nightlight, 1-Circuit

User-selectable Vacancy or Occupancy, 1-Circuit

User-selectable Vacancy or Occupancy, 2-Circuit

Technology

Dual (PIR/Ultrasonic)

PIR
Color White White or Ivory
Requires Neutral Connection Yes
No
Mounting Height 4 to 5'        
Operating Voltage

120/277, 50/60 Hz

120 VAC, 60 Hz

120/277 VAC, 60 Hz

Resistive

800 W, 120 VAC, 60 Hz

Inductive Ballast

800 VA, 120 VAC, 60 Hz

800 VA, 120 VAC; 1600 VA, 277 VAC, 60 Hz

Electronic Ballast

5 A, 120/277 VAC, 50/60 Hz





Tungsten/Incandescent

800 W, 120 VAC, 50/60 Hz

800 W, 120 VAC, 60 Hz

Motor

1/4 HP, 120 VAC @ 50/60 Hz

1/4 HP, 120 VAC @ 60 Hz

Coverage Pattern

180°

1200 ft2 PIR

400 ft2 Ultrasonic

180°

1200 ft2 PIR

Adjustable Light Level

10 fc to Daylight

30 lux to Daylight

Adjustable Time Delay

15 sec to 30 min

Operating Temp

32° F to 122° F (0° C to 50° C)

32° F to 131° F (0° C to 55° C)


Commercial-Grade Ceiling-Mount Sensor Comparison Guide

 
LED
 IOS-CMP-DT-U IOS-CMP-U  IOS-HB-U
IOS-CMP-DT-LV
IOS-CMP-LV
Model # IOS-CMP-DT-U IOS-CMP-U IOS-HB-U IOS-CMP-DT-LV* IOS-CMP-LV
Switch Type

Occupancy

Occupancy, High Bay

Occupancy, Low Voltage

Technology Dual (PIR/Ultrasonic) PIR
Dual (PIR/Ultrasonic) PIR
Color White
Requires Neutral Connection Yes
No No
Mounting Height 8 to 11'
15 to 50' 8 to 11'
Operating Voltage

120/277 VAC, 50/60 Hz

120-277 VAC, 60 Hz

24 VDC

Resistive

10 A, 120 VAC, 60 Hz


Inductive Ballast

20 A, 120/240/277 VAC*

Electronic Ballast

5 A, 120/277 VAC, 50/60 Hz

800 VA, 120 VAC, 60 Hz;
1600 VA, 277 VAC, 60 Hz


Tungsten/Incandescent

800 W, 120 VAC, 50/60 Hz

800 W, 120 VAC, 60 Hz

15A, 120 VAC**

Motor

1/4 HP, 120 VAC, @ 50/60 Hz

1/4 HP, 120 VAC @ 60 Hz

1 HP, 120/240 VAC*

1 HP, 120/240 VAC*

Coverage Pattern

360°

1600 ft2 PIR

1000 ft2 Ultrasonic

360°

1200 ft2 PIR

360°

1200 ft2 Lens 1

2800 ft2 Lens 2

360°

1600 ft2 PIR

1000 ft2 Ultrasonic

360°

1200 ft2 PIR

Adjustable Light Level

10 fc to Daylight

10 fc to 150 fc

10 fc to Daylight

10 fc to 150 fc

Adjustable Time Delay

5 sec to 30 min

15 sec to 30 min

5 sec to 30 min

15 sec to 30 min

Operating Temp

32° F to 122° F (0° C to 50° C)

32° F to 131° F (0° C to 55° C)

32° F to 122° F (0° C to 50° C)

IOS-CMP-DT-LV is LED compatible in conjunction with the IOS-PP24
** Ratings of Low Voltage Power Pack, IOS-PP24.


Residential Grade In-Wall Sensor Comparison Guide


  IOS-DSIMF
IOS-DSIF
IOS-DPBIMF
IOS-DPBIF
IOS-DPBIF2
Model # IOS-DSIMF IOS-DSIF IOS-DPBIMF IOS-DPBIF IOS-DPBIF2
Switch Type
Occupancy, Manual Override
Occupancy
Vacancy
Technology PIR
Applications

Laundry Room, Closets, Kitchen, Home Office, Bathrooms

Color

White or Ivory

Requires Neutral Wire No Yes No Yes
Mounting Height

4 to 5'

Operating Voltage

120 VAC, 60 Hz

Resistive

500 W, 120 VAC32° F to 122° F (0° C to 50° C) 60 Hz

Inductive Ballast

500 VA, 120 VAC, 60 Hz

Incandescent

500 W, 120 VAC, 60 Hz

Motor

1/8 HP, 120 VAC

Coverage Pattern

150°, 980 ft2

Adjustable Light Level

30 lux to Daylight

Adjustable Time Delay

15 sec to 30 min

Operating Temp

32° F to 131° F (0° C to 55° C)